OPERATION AND MAINTENANCE MANUALEMIproMICROPROCESSORClearPrg Selonalarmlineon/off alarm enter
4 - DESCRIPTION AND CONFIGURATION OF THE PARAMETERSOperation and maintenance manual EMIpro MICROPROCESSOR Rev. 0 dtd 02/’02/ Probes Typ
Operation and maintenance manual EMIpro MICROPROCESSOR Rev. 0 dtd 02/’0210r Regulator Type Min. Max. U.o.M. Default Value 1 Temp
Operation and maintenance manual EMIpro MICROPROCESSOR Rev. 0 dtd 02/’02* If used in condensation the fan is kept at minimum even belo
Operation and maintenance manual EMIpro MICROPROCESSOR Rev. 0 dtd 02/’0212P Alarm Type Min Max U.o.M. Default Value 1 Flow alarm
Operation and maintenance manual EMIpro MICROPROCESSOR Rev. 0 dtd 02/’02H General Type Min Max U.o.M. Default Value 5 Operating
5 - CLOCK, TIME BANDS AND ALARM LOG5.1 Clock5.1.1 Time display5.1.2 Time sFunctions enabled only with the clock board memory installed.Pressing the
5.2 5.2.1 Time bandsEntering the parameter rt (see USER parameter modification) allows the selection of rt= 1 or 2, enabling the time band function. P
The display includes an incremental index in the right-hand field, which identifies the current position; the hundreds then appear in the field on the
8 - ALARMS AND SIGNALSIn the event of an alarm, the machine performs the following actions:activates the buzzer and display , (if enabled and
8.1 Table of alarm18Operation and maintenance manual EMIpro MICROPROCESSOR Rev. 0 dtd 02/’02n. Code Description 1 E1 probe B1 2 E2
1 Page 21.1 Page 22 EMIPRO USER INTERFACE Page 22.1 The display Page 22.2 Operating indicators Page 42.3 Page 42.4 I/O Card (inpu
8.2 and descriptionAlarm signals All the alarms, except for the generic external alarm (AL), configured by parameter Pb, and the clock, are det
F1: dirty filterSignal-only alarm. No outputs are deactivated.FL: air flow alarmAlarm delayed by parameters P1 and P2.The activation of this alarm cau
tC: compressor thermal overload alarmImmediate alarm, causes the instant switching off of the compressor.This is managed only if parameter H5= 1 or 5
1 - GENERAL CHARACTERISTICS1.1 General descriptionThe EMIpro is an electronic control for the complete management of precision air-conditioners, bot
Ambient temperature, when programming it displays the value of the parametersTemperature unit of measure: degrees Centigrade/Fahrenheit.Ambient humidi
2.2 Operating (Picture 3).indicatorsThe main states of the regulator are displayed to the user through 3 Led on the front panel4Picture 3led LINE (y
Operation and maintenance manual EMIpro MICROPROCESSOR Rev. 0 dtd 02/’022.4 I/O Card (Input/Output)Picture 5 depicts the I/O Card.The
6Operation and maintenance manual EMIpro MICROPROCESSOR Rev. 0 dtd 02/’02Table 1 - I/O Inputs and outputsDigital inputs - Connector 2
3 - PROGRAMMING PARAMETERS AND THEIR MODIFICATION3.1 ParametersThe parameters are divided into 3 levels, each of them contains the previous, which th
111Once having entered any level of parameters, one pressing of the button displays the value, flashing, of the Parameter selected, wh